16 CompactLogix Isolated Analog Input Module

Publication 1769-IN074C-EN-P - March 2011

Configuration Data File

The manipulation of the bits from this file is normally done with programming software (for
example, RSLogix 5000 or RSNetWorx for DeviceNet software) during initial configuration of
the system. In that case, graphical screens are provided by the programmer to simplify
configuration. However, some systems, like the 1769-ADN DeviceNet adapter, also allow the
bits to be altered as part of the control program, using communication rungs. In that case, it is
necessary to understand the bit arrangement.

Configuration Data Array

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Real Time Sample Value

1

ETS

Reserved

2

EC

Reserved

EA

AL

EI

Reserved

Input Filter Sel Chl0

3

Reserved

Inpt Dta Fm

Chl0

Reserved

Inpt Tp/RngeSel Chl0

4

S

Process Alarm High Data Value Channel 0

5

S

Process Alarm Low Data Value Channel 0

6

S

Alarm Dead Band Value Channel 0

7

Reserved

8

EC

Reserved

EA

AL

EI

Reserved

Inpt Filter Sel Chl1

9

Reserved

Inpt Dta Fm

Chl1

Reserved

Inpt Tp/RngeSel Chl1

10

S

Process Alarm High Data Value Channel 1

11

S

Process Alarm Low Data Value Channel 1

12

S

Alarm Dead Band Value Channel 1

13

Reserved

14

EC

Reserved

EA

AL

EI

Reserved

Input Filter Sel Chl2

15

Reserved

Inpt Dta Fm

Chl2

Reserved

Inpt Tp/RngeSel Chl2

16

S

Process Alarm High Data Value Channel 2

17

S

Process Alarm Low Data Value Channel 2

18

S

Alarm Dead Band Value Channel 2

19

Reserved

20

EC

Reserved

EA

AL

EI

Reserved

Input Filter Sel Chl3

21

Reserved

Inpt Dta Fm

Chl3

Reserved

Inpt Tp/RngeSel Chl3

22

S

Process Alarm High Data Value Channel 3

23

S

Process Alarm Low Data Value Channel 3