Labeling the Terminals

A removable, write-on label is provided with the module. Remove the label from the door, mark
the identification of each terminal with permanent ink, and slide the label back into the door.
Your markings (ID tag) will be visible when the module door is closed.

Removing the Finger-safe Terminal Block

When wiring field devices to the module, it is not necessary to remove the terminal block. If you
remove the terminal block, use the write-on label on the side of the terminal block to identify the
module slot location and type. RTB position can be indicated by circling either the ‘R’ for right
side or ‘L’ for left side.

To remove the terminal block, loosen the upper and lower retaining screws. The terminal block
will back away from the module as you remove the screws. When replacing the terminal block,
torque the retaining screws to 0.46 N•m (4.1 lb•in).

Wiring the Finger-safe Terminal Block

When wiring the terminal block, keep the finger-safe cover in place.

1.

Loosen the terminal screws to be wired.

2.

Route the wire under the terminal pressure plate.

WARNING: When you connect or disconnect the removable terminal block (RTB)
with field side power applied, an electrical arc can occur. This could cause an
explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

Wiring the
finger-safe
terminal block

Upper Retaining Screw

Lower Retaining Screw

Advertising