1.

Disconnect power.

2.

Check that the bus lever of the module to be installed is in the unlocked (fully right)
position.

3.

Use the upper and lower tongue-and-groove slots (1) to secure the modules together (or
to a controller).

4.

Move the module back along the tongue-and-groove slots until the bus connectors (2)
line up with each other.

5.

Push the bus lever back slightly to clear the positioning tab (3).

Use your fingers or a small screwdriver.

6.

To allow communication between the controller and module, move the bus lever fully to
the left (4) until it clicks.

Be sure it is locked firmly in place.

7.

Attach an end cap terminator (5) to the last module in the system by using the
tongue-and-groove slots as before.

8.

Lock the end cap bus terminator (6).

Mounting Expansion I/O

ATTENTION: When attaching I/O modules, it is very important that the bus
connectors are securely locked together to ensure proper electrical connection.

IMPORTANT

A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end
of the communication bus.

ATTENTION: During panel or DIN rail mounting of all devices, be sure that all
debris (such as metal chips or wire strands) is kept from falling into the module.
Debris that falls into the module could cause damage on power up.

ATTENTION: When used in a Class I, Division 2, hazardous location, this
equipment must be mounted in a suitable enclosure with proper wiring method
that complies with the governing electrical codes.