CompactLogix Isolated Analog Input Module 19
Publication 1769-IN074C-EN-P - March 2011
Temperature, operating
•
IEC 60068-2-1 (Test Ad, Operating Cold)
•
IEC 60068-2-2 (Test Bd, Operating Dry
Heat)
•
IEC 60068-2-14 (Test Nb, Operating
Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating
•
IEC 60068-2-1 (Test Ab, Unpackaged
Nonoperating Cold)
•
IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat)
•
IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp
Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
5 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
20 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Emissions
CISPR 11
Group 1, Class A
ESD immunity
IEC 61000-4-2
4 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from
80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900
MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890
MHz
3V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±2 kV at 5 kHz on signal ports
Environmental Specifications 1769-IF4I
Attribute
1769-IF4I