ControlNet Coax Taps 13

Rockwell Automation Publication 1786-IN007C-EN-P - October 2010

Connect Taps with Trunk Cable

You can increase the distance between T-taps or between Y-taps by using
sections of trunk cable between taps to create a segment. Connecting taps by
using this method requires BNC connectors (included) and cable (not
included) with the tap kit.

Connect Taps with Barrel Connectors

You can connect T-taps installed on one DIN rail by using barrel (plug-to-plug)
connectors. T-taps connected with barrel connectors (catalog no. 1786-BNCP)
require horizontal mounting of the taps on one DIN rail.

IMPORTANT

Do not use barrel connectors to connect taps on separate DIN
rails.

Barrel connectors should be used only if taps are securely
mounted on (but not screwed or bolted to) the DIN rail. If you are
using barrel connectors, use the universal mounting bracket with
a transition plate. to mount the taps to the DIN rail.

Insecure mounts or use of barrel connectors between multiple
DIN rails may result in loose connections and tap failure.

Segment

31879-M