Mount to din rail – Rockwell Automation 1786-TPYS ControlNet Coax Taps Installation Instructions User Manual

Page 7

Advertising
background image

ControlNet Coax Taps 7

Rockwell Automation Publication 1786-IN007C-EN-P - October 2010

Mount to DIN Rail

Use the following procedure to mount a T-tap or Y-tap to a DIN rail.

1.

Determine if your installation requires the use of the transition plate.

The transition plate should be used only when a T-tap is being installed
and the T-tap needs to be mounted horizontally.

If you are not using the transition plate, skip to

step 4

.

2.

Begin attaching the transition plate by aligning the holes of the
transition plate and tap body.

3.

Insert the threaded screws into holes of the transition plate and tighten.

IMPORTANT

Do not over-tighten screws as tap body damage may result.
Applied screw torque should not exceed 0.2…0.4 N

m

(0.14…0.29 lb

ft).

31642

Advertising