Wire Requirements

Wiring Recommendation

The MicroLogix 1100 controllers have screw-cage clamps on the input and output
terminal blocks. With screw-cage clamp terminal blocks, there is no need to attach
additional hardware such as a spade lug to the wire, or use a finger-safe cover.

Follow these steps to wire the terminal block.

1. Strip the end of the wire.

The recommended length for the stripped end of the wire is 11.0 mm
(0.440 in.).

Wire Type

Wire Size (2 wire maximum per terminal)

1 wire per terminal

2 wire per terminal

Solid

Cu-90 °C (194 °F)

12...20 AWG

16...20 AWG

Stranded

Cu-90 °C (194 °F)

14...20 AWG

18...20 AWG

Wiring torque = 0.56 Nm (5.0 in-lb) rated.

ATTENTION

Be careful when stripping wires. Wire fragments that fall into the controller could
cause damage. Once wiring is complete, be sure the controller is free of all metal
fragments before removing the protective debris strip. Failure to remove the strip
before operating can cause overheating.

Input Terminal Block

Output Terminal Block

DC

COM

NOT

USED

+ 12/24V -

DC IN

NOT

USED

I/1

I/0

I/2

I/3

DC

COM

I/4

I/5

IA

COM

IV1(+)

IV2(+)

I/6

I/7

I/8

I/9



VAC

O/0

VDC

VAC

O/1

VDC

VAC

O/2

VDC

VAC

O/3

VDC

VAC

O/4

VDC

VAC

O/5

VDC

NOT

USED

NOT

USED

1763-L16DWD

Advertising