General, Relay contact ratings – Rockwell Automation 1763-L16xxx MicroLogix 1100 Programmable Controllers Installation Instructions User Manual

Page 27

Advertising
background image

27

Publication 1763-IN001B-EN-P - September 2007

Output Specifications For Ordinary (Non-Hazardous) Locations only

General

Description

1763

-L16AWA, -L16BWA,
-L16DWD

-L16BBB

Relay and FET Outputs

Maximum Controlled Load

1440 VA

720 VA

Maximum Continuous Current:

Current per Group Common

5A

5A

Current per Controller

at 150V max

30 A or total of per-point loads, whichever is less

at 240V max

20 A or total of per-point loads, whichever is less

Relay Outputs

Turn On Time/Turn Off Time

10 msec (maximum)

(1)

(1)

Scan time dependent.

Load Current

10 mA (minimum)

Relay Contact Ratings

Maximum Volts

Amperes

Amperes
Continuous

Volt-Amperes

Make

Break

Make

Break

240V ac

15.0 A

1.5 A

5.0 A

(1)

(1)

3.0 A above 40 °C.

3600 VA

360 VA

120V ac

30.0 A

3.0 A

3600 VA

360 VA

125V dc

0.22 A

1.0 A

28 VA

Advertising