Output Specifications For Ordinary (Non-Hazardous) Locations only
General
Description
1763
-L16AWA, -L16BWA,
-L16DWD
-L16BBB
Relay and FET Outputs
Maximum Controlled Load
1440 VA
720 VA
Maximum Continuous Current:
Current per Group Common
5A
5A
Current per Controller
at 150V max
30 A or total of per-point loads, whichever is less
at 240V max
20 A or total of per-point loads, whichever is less
Relay Outputs
Turn On Time/Turn Off Time
10 msec (maximum)
(1)
(1)
Scan time dependent.
Load Current
10 mA (minimum)
Relay Contact Ratings
Maximum Volts
Amperes
Amperes
Continuous
Volt-Amperes
Make
Break
Make
Break
240V ac
15.0 A
1.5 A
5.0 A
(1)
(1)
3.0 A above 40 °C.
3600 VA
360 VA
120V ac
30.0 A
3.0 A
3600 VA
360 VA
125V dc
0.22 A
1.0 A
28 VA