Several specific steps can be taken to help reduce the effects of environmental
noise on analog signals:

• install the MicroLogix 1100 system in a properly rated (NEMA) enclosure.

Make sure that the MicroLogix 1100 system is properly grounded.

• use Belden cable #8761 for wiring the analog channels, making sure that the

drain wire and foil shield are properly earth grounded.

• route the Belden cable separately from any ac wiring. Additional noise

immunity can be obtained by routing the cables in grounded conduit.

Grounding Your Analog Cable

Use shielded communication
cable (Belden #8761). The
Belden cable has two signal
wires (black and clear), one
drain wire, and a foil shield.
The drain wire and foil shield
must be grounded at one end
of the cable.

IMPORTANT

Do not ground the drain wire and foil shield at both ends of the cable.

Foil Shield

Black Wire

Drain Wire

Clear Wire

Insulation