Working voltage, Bbb fet output specifications – Rockwell Automation 1763-L16xxx MicroLogix 1100 Programmable Controllers Installation Instructions User Manual

Page 29

Advertising
background image

29

Publication 1763-IN001B-EN-P - September 2007

Working Voltage

Turn-On Time (maximum)

0.1 ms

6 µs

Turn-Off Time (maximum)

1.0 ms

18 µs

Repeatability (maximum)

Not Applicable

2 µs

Drift (maximum)

Not Applicable

1 µs per 5 °C (9 °F)

(1)

Output 2 and 3 are designed to provide increased functionality over the other FET outputs. Output 2 and 3 may be used like
the other FET transistor outputs, but in addition, within a limited current range, they may be operated at a higher speed.
Output 2 and 3 also provide a pulse train output (PTO) or pulse width modulation output (PWM) function.

Working Voltage (1763-L16AWA)

Description

1763-L16AWA

Power Supply Input to
Backplane Isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second

265V ac Working Voltage (IEC Class 2 reinforced insulation)

Input Group to Backplane
Isolation

Verified by one of the following dielectric tests:1517V ac for 1 second or
2145V dc for 1 second

132V ac Working Voltage (IEC Class 2 reinforced insulation)

Input Group to Input Group
Isolation

Verified by one of the following dielectric tests:1517V ac for 1 second or
2145V dc for 1 second

132V ac Working Voltage (basic insulation)

Output Group to Backplane
Isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second

265V ac Working Voltage (IEC Class 2 reinforced insulation)

Output Group to Output
Group Isolation

Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1second

265V ac Working Voltage (basic insulation), 150V ac Working Voltage (IEC
Class 2 reinforced insulation)

BBB FET Output Specifications

Description

General Operationl

High Speed Operation

(1)

(Output 2 and 3 Only)

Advertising