26

Publication 1763-IN001B-EN-P - September 2007

Output Specifications For Hazardous Locations Applications
(Class I, Division 2, Groups A, B, C, D)

General

Description

1763

-L16AWA, -L16BWA,
-L16DWD

-L16BBB

Relay and FET Outputs

Maximum Controlled Load

1080 VA

360 VA

Maximum Continuous Current:

Current per Group Common

3A

3A

Current per Controller

at 150V max

18 A or total of per-point loads, whichever is less

at 240V max

18 A or total of per-point loads, whichever is less

Relay Outputs

Turn On Time/Turn Off Time

10 msec (maximum)

(1)

(1)

Scan time dependent.

Load Current

10 mA (minimum)

Relay Contact Ratings

Maximum Volts

Amperes

Amperes
Continuous

Volt-Amperes

Make

Break

Make

Break

240V ac

7.5 A

0.75 A

3.0 A

1800 VA

180 VA

120V ac

15.0 A

1.5 A

3.0 A

1800 VA

180 VA

125V dc

0.22 A

1.0 A

28 VA

Advertising