General, Relay contact ratings – Rockwell Automation 1763-L16xxx MicroLogix 1100 Programmable Controllers Installation Instructions User Manual
Page 26
26
Publication 1763-IN001B-EN-P - September 2007
Output Specifications For Hazardous Locations Applications
(Class I, Division 2, Groups A, B, C, D)
General
Description
1763
-L16AWA, -L16BWA,
-L16DWD
-L16BBB
Relay and FET Outputs
Maximum Controlled Load
1080 VA
360 VA
Maximum Continuous Current:
Current per Group Common
3A
3A
Current per Controller
at 150V max
18 A or total of per-point loads, whichever is less
at 240V max
18 A or total of per-point loads, whichever is less
Relay Outputs
Turn On Time/Turn Off Time
10 msec (maximum)
(1)
(1)
Scan time dependent.
Load Current
10 mA (minimum)
Relay Contact Ratings
Maximum Volts
Amperes
Amperes
Continuous
Volt-Amperes
Make
Break
Make
Break
240V ac
7.5 A
0.75 A
3.0 A
1800 VA
180 VA
120V ac
15.0 A
1.5 A
3.0 A
1800 VA
180 VA
125V dc
0.22 A
1.0 A
28 VA