14 DataSite Natural Gas Flow Meter and Remote Terminal Unit

Publication 1758-IN001C-EN-P - June 2011

Wiring for RS485 Serial Communications

Wire the Controller for HART Communication

The controller comes with three HART protocol communications ports, including one that is
multi-point, and can connect to thirteen HART protocol meters. The other two are
point-to-point ports, and can also collect 4…20 mA signals.

HART0 multi-point port wiring to passive meters

Master
Station

First station in network
requires terminations

Last station in network
requires terminations

RS-485 network
1200 m (4000 feet)
maximum length

D
D

Slave
Station

D
D

Slave
Station

D
D

44390

HO+

DC Power

Supply

HO-

Two Wire
Slave #13

Two Wire

Slave #2

Two Wire

Slave #1