DataSite Natural Gas Flow Meter and Remote Terminal Unit 15

Publication 1758-IN001C-EN-P - June 2011

HART1 or HART2 point-to-point wiring to passive meters

Wire the Controller for Sleep/Wake Up mode

To reduce power consumption in unattended or solar-powered applications, the controller
can be configured to enable Sleep mode, and disable Sleep mode when inputs are detected.

Ground the Module

In solid-state control systems, grounding and wire routing help limit the effects of noise due
to electromagnetic interference (EMI). Run the ground connection from the ground terminal
of the controller to the ground bus prior to connecting any devices. Use AWG #14 wire.

ATTENTION

All devices connected to the RS-232/485 communication port must be referenced to
controller ground, or be floating (not referenced to a potential other than ground). Failure
to follow this procedure may result in property damage or personal injury.

H1+

DC Power

Supply

H1-

Two Wire

Slave #1

H2+

DC Power

Supply

H2-

Two Wire

Slave #2

44393

WAKEUP

12~24V DC

27

28

29

+

-

44396