Rockwell Automation 1758-RTU202 Datasite Installation Instructions User Manual

Page 24

Advertising
background image

24 DataSite Natural Gas Flow Meter and Remote Terminal Unit

Publication 1758-IN001C-EN-P - June 2011

Output impedance

300

transformer isolated

Input impedance

4000

transformer isolated

Load resistor

250

Ω, 1 W max

Environmental Specifications

Attribute

Value

Temperature, operating

-40... 70 °C (-40 ...158 °F)

Temperature, non-operating

-50...80 °C (-58... 176 °F)

Relative humidity

5...95% non-condensing

Vibration

IEC 60068-2-6
Constant amplitude 0.15mm: 10…57 Hz
Constant acceleration 2g: 57…150 Hz

Shock

IEC 60068-2-27
18 shocks, semi-sinusoidal 15g / 11 ms

Electrical/EMC

EN 61000-6-4 2007;
EN 61000-6-2 2005

ESD immunity

IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…1000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 1000…2700 MHz

HART

Attribute

Description

Advertising