DataSite Natural Gas Flow Meter and Remote Terminal Unit 23

Publication 1758-IN001C-EN-P - June 2011

Voltage input impedance

100 k

Ω for 10V DC inputs

170

Ω for 20 mA inputs

Input Resolution

16-bit

Non-linearity

±0.1% of full scale

Overall accuracy

±0.1% of full scale at 25 °C
±0.3% of full scale over temperature range

Voltage Input Overvoltage
Protection

Continuous input must not exceed 160% of the rated range

Analog Outputs

Attribute

Description

D/A resolution ratio

16-bit

Power supply

Successive approximation

Output signal range

4…20 mA

Maximum load
Impedance

1000

Ω with 24V DC loop power

400

Ω with 12V DC loop power

Output type

Single ended regulation on positive side with common negative return

Isolation voltage

70V AC or 100V DC

Absolute accuracy

±0.2% (25 °C with 250

Ω load)

±0.5% (full temperature range, 0…1000

Ω load)

Response time

100 ms typical (10…90%)

Noise and ripple, max

0.04%

Transient protection

600 W

HART

Attribute

Description

Modulation

Frequency Shift Keying (FSK)
Logic 1 - 1200 Hz
Logic 0 - 2200 Hz

Data rate

1200 bps

Transmit level

500 mVp-p / 250

Receive sensitivity

120 mVp-p/ on
80 mVp-p/ off

Analog Inputs