Analog Voltage and Current Input and Output Ranges
Note: The analog voltage inputs are protected to withstand the application of ±24V dc
without damage to the controller. The analog current inputs are protected to withstand the
application of ±50 mA without damage.
Note: The analog outputs are protected to withstand the short circuiting of the voltage or
current outputs without damage to the controller.
Operating Range
Overrange
Underrange
–10.5V dc
10.5V dc
–24V dc
24V dc
Operating Range
Overrange
Underrange
–21 mA
21 mA
–50 mA
50 mA
Analog Voltage Input Range
Analog Current Input Range
Operating Range
0V dc
10V dc
Operating Range
20 mA
4 mA
Analog Voltage Output Range
Analog Current Output Range