88

Publication 1761-IN001C-MU-P - Septiembre 2007

Tabla de capacidad nominal de contactos de relé

Especificaciones de la salida analógica

Volts máximos Amperes

Amperes
continuos

Voltamperes

Cierre

Apertura

Cierre

Apertura

240 VCA

7.5 A

0.75 A

2.5 A

1800 VA

180 VA

120 VCA

15 A

1.5 A

125 VCC

0.22 A

(1)

(1)

For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied dc voltage. For example, 28 VA ÷ 48 VCC = 0.58A. For dc voltage applications less than 48V, the make/break ratings
for relay contacts cannot exceed 2A. For dc voltage applications greater than 48V, the make/break ratings for relay contacts
cannot exceed 1A.

1.0 A

28 VA

24 VCC

1.2 A

(1)

2.0 A

Descripción

Especificación

Rango de salida de voltaje

0 a 10 VCC -1LSB

Rango de salida de corriente

4 a 20 mA - 1LSB

Tipo de datos

Número entero con signo de 16 bits

Sin linealidad

0.02%

Respuesta de paso

2.5 ms (a 95%)

Rango de carga - salida de voltaje

1K

Ω a ∞ Ω

Rango de carga - salida de corriente

0 a 500

Ω

Codificación de 4 a 20 mA - 1 LSB, 0 a 10 VCC - 1LSB 0 a 32,767

Cableado incorrecto de la salida de voltaje

Puede resistir los cortocircuitos

Cableado incorrecto de la salida de corriente

Puede resistir los cortocircuitos

Resolución de salida

15 bits

Tiempo de establecimiento de la salida analógica

3 mseg (máximo)

Precisión general de 0°C a +55°C

±1.0% de la escala completa

Deriva de precisión general de 0°C a +55°C (máx.)

±0.28%

Error general a +25°C (+77°F) (máx.)

0.2%

Aislamiento del cableado de campo a lógica

Capacidad nominal de 30 V de operación/500 V de
aislamiento