Rockwell Automation 2706-P92C_P94C InView Message Display User Manual
Page 10
Advertising
![background image](/manuals/580150/10/background.png)
10 InView Marquee Message Display
Publication 2706-IN016D-EN-P - February 2009
5. Connect the incoming communication wires per the tables below.
TB2 is used for supplying power to the optional InView Legacy
Communication board kit.
ATTENTION
Use shielded Ethernet cable. Shielded Ethernet cable is required to maintain noise
immunity.
The 2706-P Cable1 is used for downloading messages only and must be removed after
downloading is complete.
TB1 - RS-485
1.GND
4.CH A
2.SHLD
5.CH B
3.COMM
6.TERM
TB2 - Aux +5V
1.+5V
2.GND
TB3 - RS-232
1.TXD
4.CTS
2.RXD
5.GND
3.RTS
6.EGND
RJ-12
TB3
TB2
TB1
Ethernet
Communication
Openings
Advertising