Mount the terminal in a panel, Panel cutout dimensions – Rockwell Automation 2711PC-T10C4D1 PanelView Plus Terminals and Display Modules User Manual
Page 11

PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 11
Publication 2711P-IN001I-EN-P - November 2009
Panel Cutout Dimensions
Use the full size template shipped with your terminal to mark the cutout dimensions.
Mount the Terminal in a Panel
Mounting clips secure the terminal to the panel. The number of clips you use
(4, 6, or 8) varies by terminal type.
Follow these steps to mount the terminal in a panel.
1. Cut an opening in the panel by using the panel cutout shipped with the terminal.
2. Make sure the terminal sealing gasket is properly positioned on the terminal.
Terminal Type
Height, mm (in.)
Width, mm (in.)
700 Keypad or Keypad and Touch
167 (6.57)
264 (10.39)
700 Touch
154 (6.08)
220 (8.67)
1000 Keypad or Keypad and Touch
224 (8.8)
375 (14.75)
1000 Touch
224 (8.8)
305 (12.00)
1250 Keypad or Keypad and Touch
257 (10.11)
390 (15.35)
1250 Touch
257 (10.11)
338 (13.29)
1500 Keypad or Keypad and Touch
305 (12.00)
419 (16.50)
1500 Touch
305 (12.00)
391 (15.40)
ATTENTION
Disconnect all electrical power from the panel before making the panel cutout.
Make sure the area around the panel cutout is clear.
Take precautions so metal cuttings do not enter any components already installed in
the panel.
Failure to follow these instructions may result in personal injury or damage to panel
components.