Connect ac power – Rockwell Automation 2711PC-T10C4D1 PanelView Plus Terminals and Display Modules User Manual

Page 21

Advertising
background image

PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 21

Publication 2711P-IN001I-EN-P - November 2009

Connect AC Power

Follow these steps to connect the terminal to AC power.

1. Verify that the terminal is not connected to a power source.

2. Secure the AC power wires to the terminal block.

Follow the markings on terminal blocks and terminal for proper connections.

3. Secure the protective earth ground wire to the marked position of the power input

terminal block.

4. Secure the functional earth ground wire to the functional earth ground screw on the

back of the display to ground bus.

5. Apply AC power to the terminal.

WARNING

Explosion Hazard - Do not connect or disconnect equipment while circuit is live unless
area is known to be nonhazardous.

Disconnect all power before installing or replacing components. Failure to disconnect
power may result in electrical shock and/or damage to the terminal.

ATTENTION

Improper wiring of power terminals may result in voltage at the communication
connector shells. Refer to the following figure when wiring.

Do not apply power to the terminal until all wiring connections have been made. Failure
to do so may result in electrical shock.

GND

L1

L2/Neutral

Protective Earth

to Ground Bus

Functional Earth Ground to Ground Bus

Advertising