Follow these steps to remove the terminal block.

1. Loosen the two screws that secure the terminal block.

2. Gently pull the terminal block away from the connector.

Follow these steps to install the terminal block.

1. Reattach the terminal block to the connector until seated.

2. Tighten the two screws that secure the terminal block to the connector.

DC Power Connections

DC-powered PanelView Plus devices have an integrated 24V DC power supply. Both isolated
and non-isolated power supplies have these ratings:

24V DC nominal (18…32V DC)

70 W maximum (2.9 A at 24V DC)

The power supply is internally protected against reverse polarity of the DC+ and DC-
connections. Connecting DC+ or DC- to the earth/ground terminal may damage the device.

The input power terminal block supports these wire sizes.

Wire Specifications for DC Input Power Terminal Block

Logic Module

Wire Type

Dual-wire

Gauge

(1)

(1)

Two-wire max per terminal.

Single-wire

Gauge

Terminal Screw

Torque

Series A to D

Stranded

or solid

Cu 90 °C

(194 °F)

22…16 AWG

22…14 AWG

0.23…0.34 N•m

(2…3 lb•in)

Series E and later

0.56 N•m (5 lb•in)

3-position AC or DC