Hazardous Locations

This equipment is suitable for these locations:

Class I, Division 2 Groups A, B, C, D

Class II, Division 2 Groups F, G

Class III

Ordinary, nonhazardous locations only

The following statement applies to use in hazardous locations.

The terminals have a temperature code of T4 when operating in a 55 °C (131 °F) maximum
ambient temperature. Do not install the terminals in environments where atmospheric gases
have ignition temperatures

less than 135 °C (275 °F).

WARNING

Explosion Hazard

Substitution of components may impair suitability for hazardous locations.

Do not disconnect equipment unless power has been switched off and area is
known to be nonhazardous.

Do not connect or disconnect components unless power has been switched off.

All wiring must comply with N.E.C. articles 501, 502, 503, and/or C.E.C. section
18-1J2 as appropriate.

Peripheral equipment must be suitable for the location in which it is used.