PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 25

Publication 2711P-IN001I-EN-P - November 2009

The table shows indicator states if the terminal powers on and stops during startup.

Check the Display

If the terminal display is dim or unreadable:

check the brightness setting of the display. From Configuration mode on the terminal,
access Terminal Settings>Display Intensity.

check the Screen Saver settings. The backlight may be turning off or dimming the
display unexpectedly. From Configuration mode on the terminal, access Terminal
Settings>Display>Screen Saver.

Indicator States If the Terminal Stops During Startup

Fault (Red)

Indicator

Comm (Green)

Indicator

Description

Blinking

(1)

(1)

Blinking red indicates a recoverable error.

Off

Last firmware download failed.

Reload firmware using Firmware Upgrade Wizard (FUW) utility.

Blinking

EBC boot loader firmware failed or is missing.

Reload firmware using Firmware Upgrade Wizard (FUW) utility.

On

Windows CE OS firmware failed or is missing.

Reload firmware using Firmware Upgrade Wizard (FUW) utility.

On

(2)

(2)

Solid red indicates a nonrecoverable or fatal error.

Off

Fatal hardware error occurred.

Replace the logic module.

Blinking

Fatal hardware error in display.

Replace the display module.