Input filter times, Set the fault detect switch – Rockwell Automation 1797-IBN16 FLEX Ex NAMUR Input Module User Manual

Page 12

Advertising
background image

12 FLEX Ex NAMUR Input Module

Publication

1797-5.7 - March 2010

Input Filter Times

Set the Fault Detect Switch

A switch, located on the backside of the module, lets you select the action of

the module when a fault (wire off or short circuit) is detected. Switch position

1 determines the action for channels 0 to 3, position 2 for channels 4 to 7,

position 3 for channels 8 to 11, and position 4 for channels 12 to 15.
Set the switch:

• OFF to disable fault detection for the selected channels.
• ON to enable fault detection for the selected channels.

Bits

Description

Maximum
Filter Time

02

01

00

Filter Times 00…11 (00…13)

05

04

03

Filter Times 12…15 (14…17)

0

0

0

Filter Time 0 (default)

1 ms

0

0

1

Filter Time 1

1 ms

0

1

0

Filter Time 2

2 ms

0

1

1

Filter Time 3

3 ms

1

0

0

Filter Time 4

5 ms

1

0

1

Filter Time 5

9 ms

1

1

0

Filter Time 6

17 ms

1

1

1

Filter Time 7

33 ms

Bits 00

02 also control the filter times of all 16 fault alarm bits of read word 1 when

module is in fault mode

.

OFF

1

2

3 4

OFF

1 2 3 4