18 FLEX Ex NAMUR Input Module

Publication

1797-5.7 - March 2010

• CSA C22.2 No. 30-M1986, Explosion-Proof Enclosures for Use in

Class I Hazardous Locations

• CSA-E79-0-95, Electrical Apparatus for Explosive Gas Atmospheres,

Part 0: General Requirements

• CSA-E79-11-95, Electrical Apparatus for Explosive Gas

Atmospheres, Part 11: Intrinsic Safety “i”

• CSA C22.2 No. 14-95, Industrial Control Equipment

Table 1

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).

Table 2

The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a
system when the approved values of V

t

and I

t

of the associated apparatus are

less than or equal to V

oc

and I

sc

or V

max

and I

max

of the intrinsically safe

apparatus and the approved values of C

a

and L

a

of the associated apparatus

are greater than C

i

+ C

cable

and L

i

+ L

cable

respectively for the intrinsically safe

apparatus.

Wiring
Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

μF) L

a

(mH)

1 and 2

Any one
channel (for
example,
ch0)

0(+), 1(-)

14.5

15

-

-

A, B

0.3

80.0

C, E

0.9

320.0

D, F, G

2.4

640.0

Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

μF)

L

a

(

μH)

Male Bus
Connector

5.8

400

A-G

3.0

3.0