Rockwell Automation 1797-IBN16 FLEX Ex NAMUR Input Module User Manual

Page 16

Advertising
background image

16 FLEX Ex NAMUR Input Module

Publication

1797-5.7 - March 2010

Environmental

Attribute

Value

Temperature, operating

-20…70 °C (-4…+158 °F)

Temperature,
nonoperating

-40…85 °C (-40…185 °F)

Relative humidity

5…95% noncondensing

Vibration

Tested 2 g @ 10…500 Hz per IEC68-2-6

Shock, operating

Tested to 15 g peak acceleration, 11(+1) ms pulse width

Shock, nonoperating

Tested to 15 g peak acceleration, 11(+1) ms pulse width

Agency Certification

Attribute

Value

CENELEC

II (1) 2G Ex ib[ia] IIC T4

II (1) D [Ex iaD]

U, C-UL

Class I, Groups A, B, C and D; Class II, Groups E, F and G;

Class III hazardous Locations.

Class I, Zone 1, AEx ib[ia] IIC T4.

FM

Intrinsically safe Class I, Div 1, Groups A, B, C, D, T4.

Associated Apparatus with intrinsically safe

Connections Class I, II, III, Div 1, Groups A--G

Intrinsically safe Class I, Zone 1, AEx ib[ia] IIC T4.

IECEx

[Zone 0] Ex ib[ia] IIC T4

[Ex iaD]

INMETRO

BR-Ex ia/ib IIB/IIC T4

Certificate of Conformity

Attribute

Value

CENELEC

DMT 98 ATEX E013 X

U, C-UL

UL, C-UL File Number E197983

Advertising