Table 2 – Rockwell Automation 1797-IBN16 FLEX Ex NAMUR Input Module User Manual

Page 23

Advertising
background image

FLEX Ex NAMUR Input Module 23

Publication

1797-5.7 - March 2010

Table 2

The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a
system when the approved values of V

oc

and I

sc

or V

t

and I

t

of the associated

apparatus are less than or equal to V

max

and I

max

of the intrinsically safe

apparatus and the approved values of C

a

and L

a

of the associated apparatus

are greater than C

i

+ C

cable

and L

i

+ L

cable

respectively for the intrinsically safe

apparatus. The internal capacitances Ci of the terminal base must be taken
into account to verify the intrinsic safety.

Simple apparatus is defined as a device which neither generates nor

stores more than 1.2V, 0.1 A, 20 μJ, or 25 mW.

Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505. For additional information refer to
ANSI/ISA RP12.6.

This module, 1797-IBN16, must be used with terminal base 1797-TB3

or 1797-TB3S.

Terminals 36 to 39, and 46 to 49 shall not be connected.

Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

μF)

L

a

(

μH)

Male Bus
Connector

5.8

400

A-G

3.0

3.0

WARNING

Substitution of components may impair intrinsic safety.

AVERTISSEMENT

La substitution de composant peut compromettre la securite
intrinseque.

Advertising