Wiring to a 1797-tb3 or -tb3s terminal base unit – Rockwell Automation 1797-IBN16 FLEX Ex NAMUR Input Module User Manual

Page 8

Advertising
background image

8 FLEX Ex NAMUR Input Module

Publication

1797-5.7 - March 2010

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the 1797-TB3 or 1797-TB3S terminal base unit as shown
below.

1. Connect the individual input wiring to (+) terminals (0, 2, 4, 6, 8, 10,

12, 14) on the 0 to 15 row (A) and on the 16 to 33 row (B) (terminals
17, 19, 21, 23, 25, 27, 29, 31)as indicated in the table below.

2. Connect the associated input to the corresponding (-) terminal (1, 3,

5, 7, 9, 11, 13, 15) on the 0 to 15 row (A), and on the 16 to 33 row (B)
(terminals 18, 20, 22, 24, 26, 28, 30, 32) for each input as indicated in
the table below.

3. Connect +V dc power to terminal 34 on the 34 to 51 row (C).

4. Connect -V to terminal 35 on the 34 to 51 row (C).

WARNING

Make certain that you power this module with an intrinsically safe power
supply. Do not exceed the values listed in the specifications for this module.
If you connect or disconnect wiring while the field-side power is on, an
electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.

41504

Row A

Row B

Row C

+

+

+

+

-

-

-

-

ch0

ch1

ch2

ch3

+V -V

0

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

No connections allowed to terminals 36 or 49.

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

+

-

+

-

+

-

+

-

ch7

ch6

ch5

ch4

+

-

+

-

+

-

+

-

+ -

+

-

+

-

+

-

ch8

ch9

ch10

ch11

ch15

ch14

ch13

ch12

+V

-V