Specifications – Rockwell Automation 1797-IBN16 FLEX Ex NAMUR Input Module User Manual
Page 14

14 FLEX Ex NAMUR Input Module
Publication
1797-5.7 - March 2010
Specifications
1797-IBN16 16 NAMUR Input Module
Attribute
Value
Number of inputs
16 (1 group of 16), nonisolated, sinking
IS input type
Ex ia IIB/IIC T4,
AEx ia IIC T4,
Class I, II, III Division 1 Group A-G T4
IS module type
Ex ib IIB/IIC T4,
AEx ib IIC T4,
Class I, Division 1 Group A-D T4
Input type
NAMUR compatible
ON-state current
2.1 mA
OFF-state current
1.2 mA
Hysteresis
0.2 mA
Input frequency
1000 Hz max
Input pulse width
>500 µs on or off
Max load voltage
U/V = 7.5V DC
Short circuit current
I = 7.5 mA
Short circuit threshold
I > 6 mA
Lead breakage threshold
I < 0.35 mA
Input delay times
OFF to ON
ON to OFF
1 ms, 2 ms, 3 ms, 5 ms, 9 ms, 17 ms, 33 ms
1 ms, 2 ms, 3 ms, 5 ms, 9 ms, 17 ms, 33 ms
1 ms default - selectable thru output image table (see
Setting Input Filter Times)
Indicators (field side
indication, customer device
driven)
16 yellow status indicators
16 red fault indicators
1 green module power indicator