Entity parameters, Ce/cenelec i/o entity parameters (each channel), Ul, c-ul i/o entity parameters – Rockwell Automation 1797-IBN16 FLEX Ex NAMUR Input Module User Manual

Page 17

Advertising
background image

FLEX Ex NAMUR Input Module 17

Publication

1797-5.7 - March 2010

Entity Parameters

CE/CENELEC I/O Entity Parameters (Each Channel)

UL, C-UL I/O Entity Parameters

If this product has the UL/C-UL mark, it has been designed, evaluated,
tested, and certified to meet the following standards:

• UL 913, 1988, Intrinsically Safe Apparatus and Associated Apparatus

for Use in Class I, II, and III Division 1, Hazardous (Classified)
Locations

• UL 1203, Explosion-Proof and Dust-Ignition-Proof Electrical

Equipment for Use in Hazardous (Classified) Locations

• UL 2279, Electrical Equipment for Use in Class I, Zone 0, 1, and 2

Hazardous (Classified) Locations

• UL 61010, UL Standard for Safety Electrical Equipment For

Measurement, Control, and Laboratory Use; Part 1: General
Requirements

• CSA C22.2 No. 157-92, Intrinsically Safe and Non-Incendive

Equipment for Use in Hazardous Locations

FM

FM Certificate Number 3009806

INMETRO

05/UL-BRAE-0012X

IECEx

IECEx BVS 09.0027X

Protection

Group

Allowed
Capacitance

Allowed
Inductance

L

o

/R

o

Ratio

U

o

< 14.5V

I

o

< 15 mA

P

o

< 40 mW

Characteristic:
linear

Ex ia

IIB

1

μF

10 mH

2.6 mH/

Ω

Ex ia

IIC

300 nF

2 mH

0.65 mH/

Ω

Certificate of Conformity

Attribute

Value