14

It’s recommended that you use the RS-232 port for transferring
applications. On DTAM Plus versions with a Comm (RS-485 /
RS-232) port, you can also download applications using an RS-485
connection.

RS-485 / RS-232 Connector

(9 Pin Female)

Remote I/O Connector

(Terminal Block)

Power Connector

Remote I/O Version With

Comm Port

Versions with a Comm Port

Versions with a Comm Port

and Printer Port

Printer Port

RS-485 / RS-232 Connector

(9 Pin Female)

RS-485 / RS-232 Connector

(9 Pin Female)

Power Connector

Power Connector

To Computer
RS-485 Port or
Converter

Create your own cable

To download through the RS-485 port, you must:

set DIP switch position SW-2 ON

create a communication cable. The RS-485 port connections are:

DTAM Plus Comm Port

RS-485/RS-232 Connector

Pin 1 = Tx485 -
Pin 2 = Tx485 +
Pin 3 = Rx485 -
Pin 4 = Rx485 +