The following wire and cable length restrictions apply to DTAM
products that are CE marked when used in installations that require
compliance to European EMC Directive 89/336:

DC Power Wiring

10 meters

Ground Terminal Wire

3 meters

Communication Cables

30 meters

These restrictions apply to catalog numbers 2707–L8P1 Series D,
2707–L40P1 Series D and 2707–V40P1 Series D.

The DTAM Plus accepts supply voltages in the following ranges
depending upon the power supply designation.

Versions with P1 power supply, accept 15-23V AC (47 to 440 Hz)
or 20-30V DC

Series D versions with P1 Power supply only, accepts 20–30 V
DC

Versions with P2 power supply, accept 85-265V AC (47 to 440
Hz) or 110-300V DC

Versions with P4 power supply, accept 11-13V DC

To connect the DTAM Plus to a power source:

!

ATTENTION: Verify that the power is disconnected from the
power source before wiring. Failure to disconnect power may
result in electrical shock.
Make sure that the supply voltage to the DTAM Plus is correct,
refer to the voltage label on back of unit. The incorrect voltage
may damage the DTAM Plus.

Do not overtighten the power connector screw terminals.
Overtightening the terminals may damage the DTAM Plus.

1. Make sure that the voltage source is not turned on.

2. Use AWG#16 or #14 stranded wire to connect the DTAM Plus

screw terminals to the power source (see below).

Note: The power supply terminal block on the DTAM Plus is not
removeable.

Wire and Cable Length
Restrictions

Connecting Power