3

!

ATTENTION:
EXPLOSION HAZARD: SUBSTITUTION OF
COMPONENTS MAY IMPAIR SUITABILITY FOR
CLASS 1, DIVISION 2.

RISQUE D’EXPLOSION: LA SUBSTITUTION DE
COMPOSANTS PEUT RENDRE CE MATÉRIEL
INACCEPTABLE POUR LES EMPLACEMENTS DE
CLASSE 1, DIVISION 2.

!

ATTENTION: USE P1 POWERED UNITS ONLY
WITH CLASS 2 POWER SOURCE LIMITED TO 30
VDC OPEN CIRCUIT AND 8A SHORT CIRCUIT.

ATTENTION: UTILISER AVEC UNE TENSION
D’ALIMENTATION CLASSE 2 DE 30 VCC MAXI
EN CIRCUIT OUVERT AVEC UN COURANT DE
COURT-CIRCUIT DE 8A MAXI.

!

ATTENTION:
EXPLOSION HAZARD: DO NOT CONNECT OR
DISCONNECT EQUIPMENT WHILE CIRCUIT IS
LIVE UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS.

RISQUE D’EXPLOSION: NE PAS BRANCHER
OU DEBRANCHER TANT QUE LE CIRCUIT EST
SOUS TENSION, A MOINS QU’IL NE S’AGISSE
D’UN EMPLACEMENT NON DANGEREUX.

The terminal must be mounted in a panel or enclosure to protect the
internal circuitry. The terminal meets NEMA Type 4, 12, 13 (indoor
use only) or 4X (indoor 2707-V40P2N, -V40P2NR) ratings only
when mounted in a panel or enclosure with the equivalent rating.

Allow enough spacing within an enclosure for adequate ventilation.
For some applications, you may have to consider heat produced by
other devices within a panel. The ambient temperature around the
terminal must be maintained as specified. See Specifications Section
for ratings.

Make sure that provisions are made for accessing the back panel of
the terminal for wiring, routine maintenance, and troubleshooting.

Enclosures