Hazardous locations – Rockwell Automation 6186-Mxxx Industrial Monitors Installation Instructions User Manual

Page 3

Advertising
background image

Industrial Monitors 3

Publication 6186M-IN001L-EN-P - July 2008

Hazardous Locations

This equipment is suitable for hazardous locations specified on the product
nameplate:

Class I, Division 2 Groups A, B, C, D.

Class II, Division 2 Groups F, G.

Class III, Division 1.

nonhazardous locations.

The following statement applies to use in hazardous locations.

The monitors and AC adapter have an operating temperature code of T4 when
operating in a 50 °C (122 °F) ambient environment. Do not install the product in
environments where atmospheric gases have an ignition temperature less than
135 °C (275 °F).

WARNING

Explosion Hazard

Substitution of components may impair suitability for hazardous locations.

Do not disconnect equipment unless power has been switched off and area
is known to be nonhazardous.

Do not connect or disconnect components unless power has been switched
off.

All wiring must comply with N.E.C. articles 501-4(b), 502-4(b), 503-3(b) as
appropriate.

Peripheral equipment must be suitable for the location in which it is used.

All hazardous-location equipment must be mounted in an enclosure that is
suitably designed or rated for those specific environmental conditions that
will be present, and designed to prevent personal injury resulting from
accessibility to live parts.

Advertising