4-4 Troubleshooting and Maintenance
7. Mount the circuit board to the back of the 800T devices with the
DeviceNet terminal block oriented toward sealed connector/
conduit hole of enclosure. Use the 2 screws and plastic spacers.
Tighten circuit board mounting screws to 14 in-lbs.
8. Connect the 800T device terminals to the I/O connector using an
I/O cable. An I/O cable consists of a twisted wire pair. Each set
of contacts or pilot light connects to an I/O cable. See page 1-6
for a description of the I/O connector.
9. Plug the DeviceNet terminal block connector into the circuit
board.
10. Secure cover with the 6 mounting screws. Tighten screws to
20-in lbs.
Lamp Reflector
(Lamps only)
Locknut
Thrust Washer
Trim Washer
or Legend Plate
Cover
with Gasket
Gasket
Bonding Spring
Gasket
Orient device connection
terminals as shown above.
ATTENTION
!
Do not connect I/O pins to external devices or
control circuits. Connecting pins to these
devices will damage the circuit board.
I/O Cable
I/O Connector