Instance 4 attributes (discrete input number 4), Common services, Discrete output point objects – Rockwell Automation 2705 RediSTATION Operator Interface User Manual User Manual
Page 53: Class code: 09 hex, Class attributes, Number of instances: 2, Instance 1 attributes (discrete output number 1)

Publication 2705-UM001A-EN-P
DeviceNet Information B-9
Instance 4 Attributes (Discrete Input Number 4)
Common Services
Discrete Output Point
Objects
Class Code: 09 Hex
Class Attributes
Number of Instances: 2
Instance 1 Attributes (Discrete Output Number 1)
Attribute
ID
Access
Rule
Name
DeviceNet
Data Type
Data Value
3
Get
Input Value
BOOL
0 = OFF
1 = ON
Service
Code
Implemented
Service
Class
Instance
OE
hex
Yes
Yes
Get_Attribute_Single
Attribute
ID
Access
Rule
Name
DeviceNet
Data Type
Data Value
1
Get
Revision
UINT
1
Attribute
ID
Access
Rule
Name
DeviceNet
Data Type
Data Value
3
Get
Output Value
BOOL
0 = OFF
1 = ON
4
Get
Status
BOOL
0 = OK
1 = Fault
5
Get
Fault State
BOOL
DIP Switch 9 defines:
0 = use fault value
1 = hold last state
6
Get
Fault Value
BOOL
0 (OFF)
7
Get
Idle State
BOOL
0 = use idle state
8
Get
Idle Value
BOOL
0 (OFF)
10
Get
Flash Output
BOOL
0 = no flash
1 = flash
11
Get
Flash Rate
USINT
DIP Switch 10 defines
0 (OFF) = 1 HZ
1 (ON) = 2 HZ