Connection object, Class code: 05 hex, Class attributes – Rockwell Automation 2705 RediSTATION Operator Interface User Manual User Manual
Page 49: Number of instances: 2

Publication 2705-UM001A-EN-P
DeviceNet Information B-5
Connection Object
Class Code: 05 Hex
Class Attributes
Number of Instances: 2
Instance 1 Attributes (Explicit Message Connection)
1
xxxxxx = node address
Attribute
ID
Access
Rule
Name
DeviceNet
Data Type
Data Value
1
Get
Revision
UINT
1
Attribute
ID
Access
Rule
Name
DeviceNet
Data Type
Data Value
1
Get
State
USINT
0 = nonexistent
3 = established
5 = deferred delete
2
Get
Instance Type
USINT
0 = explicit message
3
Get
Transport Class Trigger
USINT
83
hex
4
Get
Produced Connection ID
UINT
10xxxxxx011
binary
1
5
Get
Consumed Connection ID
UINT
10xxxxxx100
binary
1
6
Get
Initial Comm
Characteristics
USINT
21
hex
7
Get
Produced
Connection Size
UINT
7
8
Get
Consumed
Connection Size
UINT
7
9
Get/Set
Expected Packet Rate
UINT
2500 msec (default),
with time resolution
of 10 msec
12
Get/Set
Watchdog Timeout Action
USINT
1 = autodelete
(default)
3 = transitions to
deferred delete
13
Get
Produced Connection
Path Length
UINT
0
14
Get
Produced Connection Path
null (no data)
15
Get
Consumed Connection
Path Length
UINT
0
16
Get
Consumed Connection Path
null (no data)