0 installation, 1 wiring, 2 initial installation – Rockwell Automation 57C409 2 Channel Analog Input Module User Manual

Page 13

Advertising
background image

3Ć1

3.0 Installation

This section describes how to install and remove the module and its

cable assembly.

3.1

Wiring

The installation of wiring should conform to all applicable codes.
To reduce the possibility of electrical noise interfering with the proper

operation of the control system, exercise care when installing the

wiring from the system to the external devices. For detailed

recommendations refer to IEEE 518.

3.2

Initial Installation

Use the following procedure to install the module:
Step 1.

Turn off power to the system. All power to the rack as well

as all power to the wiring leading to the module should be

off.

Step 2.

Mount the terminal strip (M/N 57C371) on a panel. The

terminal strip should be mounted to permit easy access to

the screw terminals. Make certain that the terminal strip is

close enough to the rack so that the cable will reach

between the terminal strip and the module.

Step 3.

Fasten field wires to the terminal strip. Typical field

connections are shown in figure 3.1.
Refer to Appendix C for the arrangement of terminal board

connections. Make sure that all field wires are securely

fastened. Note that for any voltage or current input other

than +10 volts or + 1 volt, an external resistor must be

mounted on the terminal strip.

1

2

3

USER

DEVICE

COMMON

VOLTAGE INPUT

OPTIONAL

22.1K RESISTOR

FOR +5V INPUT

Figure 3.1 Ć Typical Field Signal Connections

Advertising