3Ć3

Read register 4 to determine whether bits 8 and 10 are set,

signifying that the common clock is being driven by

another module in the rack. If they are not set, then set

registers 5 and 6 on this module to the value 64. This will

enable common clock on this module. Bits 8 and 10 on

register 4 should now be set.
Monitor registers 0 and 1. Verify that they contain numbers

proportional to the analog value on their respective

channels. This confirms that the installation is complete.

Refer to table 1 for the approximate voltages or currents

that should be read.

Table 1

value

+1V

+10V

4Ć20 ma

ă4095

+1.0V

+10.0V

20 ma

ăă819

+ă.2V

+2.0V

ă4 ma

ăăă0

0.0V

0.0V

ă0 ma

-4095

-1.0V

-10.0V

ă -

Step 9.

Determine offset and gain compensation. This is

necessary because manufacturing tolerances on the

module can result in small offset and gain differences (See

figure 3.3).

VOLTS

0

4095

10

COUNTS

CORRECTED_VALUE%

OFFSET

RAW_DATA%

Figure 3.3 Ć Offset and Gain