These can easily be compensated for in software. Perform

the following steps to determine the compensation values:
Set the analog input voltage to 0 volts. Use the I/O

MONITOR to read the digital value. This is the offset.
Set the analog input voltage to maximum. Use the I/O

MONITOR to read the digital value. Subtract the offset

calculated in the previous step from this number. The

result is the gain.
Use the following equation in your application program to

compensate the data:

CORRECTED VALUE%=(RAW DATA% Ć OFFSET%) * 4095/GAIN%

3.3

Module Replacement

Use the following procedure to replace a module:
Step 1.

Turn off power to the rack and all connections.

Step 2.

Use a screwdriver to loosen the screws holding the

connector to the module. Remove the connector.

Step 3.

Loosen the screws that hold the module in the rack.

Remove the module from the slot in the rack.

Step 4.

Place the module in the antiĆstatic bag it came in, being

careful not to touch the connectors on the back of the

module. Place the module in the cardboard shipping

container.

Step 5.

Take the new module out of the antiĆstatic bag, being

careful not to touch the connectors on the back of the

module.

Step 6.

Insert the module into the desired slot in the local rack.

Use a screwdriver to secure the module into the slot.

Step 7.

Attach the field terminal connector (M/N 57C371) to the

mating half on the module. Make certain that the

connector keys are oriented correctly and that the

connector is the proper one for this module. Use a

screwdriver to secure the connector to the module.

Step 8.

Turn on power to the rack.