Rockwell Automation 57C409 2 Channel Analog Input Module User Manual

Page 14

Advertising
background image

3Ć2

Step 4.

Take the module out of its shipping container. Take it out of

the antiĆstatic bag, being careful not to touch the

connectors on the back of the module.

Step 5.

Insert the module into the desired slot in the rack. The

module will work only in a rack that contains a processor

module. Do not attempt to use the module in a remote

rack. Use a screwdriver to secure the module into the slot.

Refer to figure 3.2.

P/S

0

1

2

3

4

5

6

7

8

9 10 11 12 13 14 15

10

Typical 10 Slot Rack

16

Typical 16 Slot Rack

Figure 3.2 Ć Rack Slot Numbers

Step 6.

Attach the field terminal connector (M/N 57C371) to the

mating half on the module. Make certain that the

connector is the proper one for this module. Use a

screwdriver to secure the connector to the module.
Note that both the module and the terminal strip connector

are equipped with keys." These keys should be used to

prevent the wrong cable from being connected to a

module in the event that the connector needs to be

removed for any reason and then reattached later.
At the time of installation, rotate the keys on the module

and the connector so that they can be connected together

securely. It is recommended that, for modules so

equipped, the keys on each successive module in the

rack be rotated one position to the right of the keys on the

preceeding module.
If you use this method, the keys on a particular connector

will be positioned in such a way as to fit together only with

a specific module, and there will be little chance of the

wrong connector being attached to a module.

Step 7.

Turn on power to the rack.

Step 8.

Verify the installation by connecting the programming

terminal to the system and running the ReSource

software. Use the I/O MONITOR function.
Set registers 7 and 8 to the value 1.