4Ć9

4.5

Restrictions

This section describes limitations and restrictions on the use of this

module.

4.5.1

Writing Data to Registers

Registers 0Ć4 are read only and may not be written to by the

application software. Attempts to write to them will cause a bus error

(severe systemerror). The following are examples fromprograms

that write to the module and should therefore be avoided:
a. Referencing the module on the left side of an equal sign in a LET

statement in a control block or BASIC task.

b. Referencing an analog input as an output in a control block

function.

4.5.2

Use in Remote I/O Racks

This module must not be used in a remote rack. A processor module

must be located in the same rack as this 2 Channel Analog Input

module.

4.5.3

Initializing or Updating Filter Registers

A minimum of 5.5 msec. is required between programming

statements used to initialize or update the filter registers (9 and 10).