2 data registers – Rockwell Automation 57C442 Data Highway Plus Interface Module User Manual

Page 21

Advertising
background image

4-3

4.1.2

Data Registers

The data image in the dual port memory appears as a subset of the
PLC-5 data table. The equivalent AutoMax and Modicon registers on
the module are shown in figure 4.3.

R/0

32

Data Highway Plus station address (0-77 octal). The value comes
from the thumbwheel switches on the faceplate and is updated
only on power-up. The module will not begin to communicate on
the network until the station address is properly set and bit 0 in
register 5 is set by the user. Note that the on-line Monitor function
in the AutoMax Programming Executive software will display the
station address in decimal or hexadecimal notation.

R/0

33

Data Highway Plus Extended Status (EXT STS) error code. Refer
to Appendix H.

R/0

34-37 Data Highway Plus active station list. This is an array of 64 bits

representing the status (1=active, O=inactive) of each station on
a Data Highway Plus network. Refer to Appendix F for
information on how this list is mapped to these registers. The
local station does not appear on this list.

38-39 Not used.

R/0

40-57 Data Highway Plus Diagnostics Counters. Refer to Appendix G.

58-60 Not used.

R/0

61

Module Software Revision Level. A value of 100 indicates version
1.00, and so on.

R/0

62-63 Interface module ID (ASCII ’GTWY’)

Multibus Access

Data HighwayPlus

(AutoMax application tasks)

Access

Read Only

Binary file B3

Read/Write

Data Highway Plus

addresses B3:0 - B3:999

AutoMax Registers 64-1063

Read/Write

Binary file B4

Read Only

Data Highway Plus

addresses B4:0 - B4:999

AutoMax Registers 1088-2087

Read/Write

Binary file B5

Read/Write

Data Highway Plus

addresses B5:0- B5:999

AutoMax Registers 2088-3087

Command Buffer Area

AutoMax Registers 3584-4095

Global Registers Area

AutoMax Registers 4096-4352

Read/Write

Integer file N7

Read/Write

Data Highway Plus

addresses N7;0 - N7:999

AutoMax Registers 4384-5383

Figure 4.3 – PLC-5 Data Image

R/W

Reg#

Description

Figure 4.2 – Status and Control Register Assignments

Advertising