Appendix e - gateway _cmd_ok@ status codes, Appendix e, Gateway _cmd_ok@ status codes – Rockwell Automation 57C442 Data Highway Plus Interface Module User Manual

Page 49

Advertising
background image

E-1

Appendix E

GATEWAY _CMD_OK@ Status Codes

The following codes are written to the variable defined as the “status” parameter
in the GATEWAY _CMD_OK@ function used to initiate Data Highway Plus
network data transfers from an AutoMax application task.

0

Operation successful

1

Invalid operation

3

Invalid length

4

Invalid offset

5

Invalid length + offset

6

Invalid destination (0-77 octal)

8

Invalid data type

9

Invalid route (equal to own address)

B

Inconsistent response

C

Module not enabled

20

Parameter specifying destination address is invalid

21

Data Highway Plus module not found or inaccessible

22

No available data path

Data Highway Plus Local and Remote Status (STS) error codes are written to the
upper byte. If the first digit is “1”, the STS code is local; if the first digit is “3”, the
STS code is remote.

11

Destination memory full, cannot accept command now

12

Destination did not acknowledge command

13

Network contention, possible duplicate station or bad cabling

14

Local Data Highway Plus port is disconnected, or no other station found

15

Timeout waiting for a reply message

16

Duplicate station detected

17

Station is off-line

18

Hardware fault

1D

Transaction number mismatch

1E

Duplicate transaction number

31

lllegal command or format

32

Host is malfunctioning and will not communicate

33

Remote station host is missing, disconnected, or shut down

34

Host could not complete function due to hardware fault

35

Addressing problem or memory protected rungs

36

Function disallowed due to command protection selection

37

A-B Processor is in program mode

38

Compatibility mode file missing or communication zone problem

39

Remote station cannot buffer command

3A

(not used)

3B

Remote station problem due to download

3C

Cannot execute command due to active IPBs

3D

not used)

3E

(not used)

3F

There is an error code in the Extended Status register
(register 33 on the Data Highway Plus Interface module).
See appendix H.