I-1
Appendix I
Converting A-B Register Numbers
to AutoMax Register and Bit Numbers
for Monitoring
The A-B registers in the dual port memory of the Data Highway Plus Interface
module may be displayed using the Monitor I/O function in the AutoMax
Programming Executive. This appendix provides a method for converting the A-B
register number to a register number recognized by the Monitor I/O application.
The following table shows the correspondence between A-B register numbers and
AutoMax register numbers.
A-B File
AutoMax
Address
Register
B3:n
64 + n
B4:n
1088 + n
B5:n
2088 + n
N7:n
4384 + n
N8:n
5384 + n
N9:n
6384 + n
N10:n
7384 + n
N11:n
8384 + n
N12:n
9384 + n
N13:n
10384 + n
N14:n 11384
+
n
N15:n
12384 + n
N16:n
13384 + n
N17:n
14384 + n
N18:n
15384 + n