4-14

05 REM

The variables that follow define

&

parameters for the

&

GATEWAY CMD OK@ function

10 COMMON B3BASE% \!

Represents the physical address of

&

starting register on the Data Highway &
Plus module to be read from

20 LOCAL DST%

\!

The address of the bridge node on

&

the local Data Highway Plus network

21 LOCAL STS%

\!

The location where the status

&

resulting from the operation is stored

22 LOCAL SZE%

\!

The number of registers to be

&

transferred

23 LOCAL CMD%

\!

The Data Highway Plus command

&

sent by the module

30 DST% = 34
31 STS% = 0
32 SZE% = 100
33 CMD% = 3
40 IF NOT GATEWAY_CMD_OK@(STS%, CMD%, DST%,

&

“!01.24.00.00.84.00.80.00.00.14.00.00.N7:0”, &
VARPTR! (B3BASE%), SZE%) THEN 20000 \! process errors

In the example above, the routing bytes were determined as
follows.Recall that the last item in the actual ”slave_reg” parameter is
the destination file address.

Byte

Value Meaning

1

LSAP

01 for a 1785-KA bridge

2

24h

3

DID_LO

00 for a 1785-KA bridge

4

DID_Hl

00 for a 1785-KA bridge

5

DNDE_LO

84h (see below)

6

DNDE_Hl

00 for a 1785-KA bridge

7

LIFETIME

80h for a1785-KA bridge

8

SID_LO

00 for a 1785-KA bridge

9

SID_HI

00 for a 1785-KA bridge

10

SNDE_HI

14h is the station number of the Data Highway
Plus module

11

SNDE_LO

00 for a 1785-KA bridge

12

NSAP

00 for a 1785-KA bridge