Appendix d – Rockwell Automation 57C442 Data Highway Plus Interface Module User Manual

Page 47

Advertising
background image

D-1

Appendix D

Data Highway Plus Interface Module

7-Segment LED Error Codes

The following error codes may be displayed on the 7-segment display.

.0

EPROM checksum failure

0

Gateway parameter error

.1

RAM checksum failure

1

Reply TNS error

.2

RAM AA failure

.3

RAM SS failure

3

Duplicate station detected

.4

RAM address line failure

4

Module not ready

.5

RAM address line clear failure

6

Invalid station address on thumbwheels

7

Module has not been enabled (register 5, bit 0)

.8

Data Highway Plus initialization failure

9

Module re-start in progress

.A

Board Reset signal

.b

Local watchdog failure

C

Local port disconnected

.d

AutoMax Processor watchdog failure

.E

Power failure

.F

Module failure

All errors except 3, 4, 6, 7, and C are fatal errors and indicate a malfunctioning
module.