12 Input/12 Output Discrete Embedded TTL I/O Module with Pulse Width Modulation and DeviceLogix

Publication 1799-IN008A-EN-P - July 2005

Refer to the following table for the word/bit definitions for the 1799-12G12GL

boards

Configure Module Parameters

The module has 11 parameters that are configurable through a DeviceNet software
configuration tool such as RSNetWorx for DeviceNet. The DeviceNet configuration
tool requires an electronic data sheet (EDS) to configure the module’s parameters.

You can find the EDS file on the ODVA Web site (www.odva.org).

Use the descriptions in the following table to help you configure the parameters.

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Produced 0

I7

I6

I5

I4

I3

I2

I1

I0

Produced 1

Reserved

Logic Enabled Reserved

Reserved

I11

I10

I9

I8

Produced 2

O7

PWM Enabled 1

O6

05

04

O3

PWM Enabled 0

O2

O1

O0

Produced 3

O15

PWM Enabled 3

O14

O13

O12

O11

PWM Enabled 2

O10

09

O8

Produced 4

NetOut 7

NetOut 6

NetOut 5

NetOut 4

NetOut 3

NetOut 2

NetOut 1

NetOut 0

Produced 5

NetOut 15

NetOut 14

NetOut 13

NetOut 12 NetOut 11

NetOut 10

NetOut 9

NetOut 8

Consumed 0 O7

O6

O5

O4

O3

O2

O1

O0

Consumed 1 O15

O14

O13

O12

O11

O10

O9

O8

Consumed 2 PWM 7

PWM 6

PWM 5

PWM 5

PWM 4

PWM 3

PWM 2

PWM 1

Where: I = Input; O = Output; PWM = Pulse Width Modulation

PWM 0 through 7 = Pulse Width Modulation percent value

Parameter

Description

AutoBaud

Enables the board to match the network’s data rate. When
enabled, Baud Rate parameter is ignored.

Input Off-to-On Filter Time

Controls the amount of time the input must be in the on
state before the board reports the input as on.

Input On-to-Off Filter Time

Controls the amount of time the input must be in the off
state before the board reports the input as off.

Output Idle State

Controls the state of each output when the DeviceNet
master is in an idle state.

Output Fault State

Controls the state of each output when the board loses
communication with the DeviceNet master.

Output Idle Value

Controls the value that outputs will have when the output
idle state is set to use idle value.