Rockwell Automation 1799-D12G12GL 12 Input/12 Output Discrete Embedded I/O User Manual
Page 16
![background image](/manuals/580798/16/background.png)
16
12 Input/12 Output Discrete Embedded TTL I/O Module with Pulse Width Modulation and DeviceLogix
Publication 1799-IN008A-EN-P - July 2005
Board Status Indicator (MOD)
Network Status Indicator (NET)
DeviceLogix Status Indicator (DS1)
Indication
Status
None
No power
Green
Blinking
Solid
Needs commissioning
Device operational
Red
Blinking
Solid
Minor fault
Critical fault
Indication
Status
None
Not on line
• Device has not completed duplicate MAC ID test yet
• Device may not be powered yet
Green
Blinking
Solid
On line/connected (Group 2 device only) the device is allocated to a master
On line/no connections
Red
Blinking
Solid
Connection timed out
Failed communication: A duplicate node address exists or module is at the wrong baud
rate
Indication
Status
None
DeviceLogix disabled
Green
Solid
Blinking
DeviceLogix enabled
Input or Output force (forced value) active