Rockwell Automation 1799-D12G12GL 12 Input/12 Output Discrete Embedded I/O User Manual

Page 16

Advertising
background image

16

12 Input/12 Output Discrete Embedded TTL I/O Module with Pulse Width Modulation and DeviceLogix

Publication 1799-IN008A-EN-P - July 2005

Board Status Indicator (MOD)

Network Status Indicator (NET)

DeviceLogix Status Indicator (DS1)

Indication

Status

None

No power

Green

Blinking

Solid


Needs commissioning

Device operational

Red

Blinking

Solid


Minor fault

Critical fault

Indication

Status

None

Not on line

• Device has not completed duplicate MAC ID test yet
• Device may not be powered yet

Green

Blinking

Solid


On line/connected (Group 2 device only) the device is allocated to a master

On line/no connections

Red

Blinking

Solid


Connection timed out

Failed communication: A duplicate node address exists or module is at the wrong baud
rate

Indication

Status

None

DeviceLogix disabled

Green

Solid

Blinking


DeviceLogix enabled

Input or Output force (forced value) active