Configure DeviceLogix Parameters

Use the Function Block Editor supplied with RSNetWorx for DeviceNet software to
configure DeviceLogix parameters.

Configure the DeviceLogix parameters listed in the following table:

Output Fault Value

Controls the value that outputs will have when the output
fault state is set to ‘use fault value.’

Consumed I/O Assembly

Lets you select size of consumed data.

Network Status Override

Lets local logic override output behavior when the module is
not online.

Comm Status Override

Allows local logic to override output behavior when
communications is faulted or idled.

Quick Start

Disables Autobaud, decreasing startup time.

TIP

For more information on using the Function Block Editor, refer to
the DeviceLogix User Manual, publication ACIG-UM001, as well
as the online help supplied with RSNetWorx for DeviceNet
software.

Parameter

Selection

Function Blocks Supported

Boolean

Latches

Timers

Counters

Maximum Number of Function Blocks in a
Configuration

72

Function Block Processing Time

2 msec/24 blocks

4 msec/28 blocks

6 msec/72 blocks

Network Input Bits

32

Network Output Bits

16

Parameter

Description